Impact SW
Modular switching technology for public address and voice alarm applications
Built to meet the highest expectations, and still user friendly, flexible and cost effective . Impact SW sets a new standard for the voice alarm industry.
The Impact system consists of two chassis, a controller that transfers network data to the amplifier, and a DCA-2.500 amplifier complemented with at least one 4E-SW6 module. The 4E-SW6 is an intelligent 2-into-6 remote controlled zone expansion and zoning module that subdivides broadcasts into a multiple of six sub-areas. The 4E-SW6 provides ‘built-in’ loudspeaker monitoring.
Unique for the Impact SW are the external 4E-SW6 remote switching devices, that features 6 lines for evacuation, alerts, paging or BGM with incorporated line monitoring. The Impact SW can also easily be expanded to 1000 speaker lines.
Product specifications
Controller
Technical basic specifications
- Controls: Evacuation and alerts | reset | silence | lamptest
- Local audio network: 3x L-net for remote control devices
- Global audio network: 2x G-net for ring connectivity to up to 255 units.
- 16-EVAC input
- 8-GPO
- Mandatory relay’s: fault | reset | silence
- 2x aux entry
- AMP link
- TCP-IP / AMP link connectivity
- Compatible with all L-net devices/modules
- Dimensions: 44x483x340mm (HxWxD)
- Weight: 2kg
- IP-rating: IP30
- RAL3011
- EN54-16
Controller-expander
Technical specifications
- Local audio network: 3x L-net for remote control devices
- Global audio network: 2x G-net for ring connectivity to up to 255 units
- Compatible with all L-net devices / modules (except for SW6 and AM448)
- Dimensions: 44x483x340mm (HxWxD)
- Weight: 2kg
- IP-rating: IP30
- RAL3011
- EN54-16
DCA2.500
Technical basic specifications
- 2ch amplifier
- 2x Aux input for local source
- AMP link for audio and data sharing with controller (RJ45)
- Max. load: 2x500W @ 100V / 70V(-3dB) / 50V(-6dB) / Low-Z max. 5A
- Frequency respond: 20 - 35kHz @ 500W/ch
- Battery charger: 4Amp
- Battery range: 30 - 100Ah
- Remote contacts for: GF/| lamptest | 2xNC
- Temperature sensor included
- AMP link patch cable included
- Dimensions: 88x483x340mm (HxWxD)
- Weight: 8kg IP-rating: IP30
- RAL3011
- EN54-16 & EN54-4
4E-SW6
Technical basic specifications
- DIN rail
- Directly connected to a single/dual output line of the C500/ DCA2.500 amplifier. The SW6 zone-extender and switching module sub-devides the signal path A & B into 6x additional surveilled speakerline outputs
- All SW6 outputs can be individually addressed and are carrying signal path A or B
- Each output can switch to internal 20kHz line surveillance generator (path C)
- Each switched output zone requires an EOL-device for line integrity detection
- Max. load: 500W per channel
- Redundant L-net link, 2xRJ45
- Addressable: 0-255
- EN54-16
Contact us
Hacousto Holland BV - 4EVAC
Industrieweg 87
2651 BC Berkel en Rodenrijs
Opening hours warehouse: 08:00-16:00